布里斯托活塞壓縮機性能排氣溫度不得超過125℃(距離壓縮機150㎜-200㎜的排氣管處),但必須比排氣壓力對應(yīng)的飽和溫度高28℃。 機殼底部中心在保溫絕熱時的溫度不得超過107.2℃,但至少比吸氣壓力對應(yīng)的飽和溫度高28℃。 電機線圈溫度用電阻法測量,測得溫度不得超過129.4℃。 吸氣溫度在戶外環(huán)境溫度高的情況下過熱度不小于2.8℃ 最低環(huán)境溫度至少應(yīng)在-29℃以上,否則會損壞壓縮機。 最大開機頻率為每小時“六開六停”。 The exhaust temperature shall not exceed 125 ℃ (at the exhaust pipe 150 mm - 200 mm away from the compressor), but it must be 28 ℃ higher than the saturation temperature corresponding to the exhaust pressure. The temperature of the bottom center of the casing during thermal insulation shall not exceed 107.2 ℃, but at least 28 ℃ higher than the saturation temperature corresponding to the suction pressure. The motor coil temperature shall be measured by resistance method, and the measured temperature shall not exceed 129.4 ℃. When the outdoor ambient temperature is high, the superheat of the suction temperature shall not be less than 2.8 ℃ The minimum ambient temperature should be at least above - 29 ℃, otherwise the compressor will be damaged. The maximum startup frequency is "six on and six off" per hour.
|